panelSLD
Win64, EnglishGeneral Usage Instructions
Create single line diagram:
This button indicates to select a point in a ViewSheet to start the drawing of the single line diagram after it shows a window called SINGLE LINE DIAGRAM with all the panelboards in the model.
This only works with a ViewSheet activity.
In the SINGLE LINE DIAGRAM, there is a list box where the user must select a panelboard, once one panel is selected the following information is shown:
- Panel name.
- Distribution System.
- Total Connected.
- Total Demand Factor.
- Total Estimated Demand.
- Total Estimated Demand Current.
All these data are project parameters of Electrical Equipment in Revit .
Then the user has the following options:
- Mains breaker: A combo box, where the user must select the type of the main breaker:
M.C.B: Main current breaker.
M.L.O: Main lugs only.
- Calculate Rating: Checkbox that calculates the parameter Rating of the Electrical Circuits of the panel selected to the 125% next size up, and the MCB Rating of the panel selected; this MCB Rating will be selected to the 100% next size up and will coordinate to the 150% to the max breaker Rating to the circuits connected.
- Spare: Checkbox to introduce the number of circuits of 20A Rating and 1 pole that will be drawing as spare.
- SPD: Checkbox to draw a surge protection device.
There are 4 kinds of families that the addin uses, with Generic Annotation category:
- circuitin: General breaker.
- circuit out Branch circuit or load circuit.
- circuitspd: Surge protection device circuit.
- circuitsimbology: Simbology.
The general breaker and load breakers show the values of the project parameters indicated in the images.
Commands
Installation/Uninstallation
The installer that ran when you downloaded this app/plug-in from Autodesk App Store will start installing the app/plug-in. OR, simply double-click the downloaded installer to install the app/plugin. You may need to restart the Autodesk product to activate the app/plug-in. To uninstall this plug-in, exit the Autodesk product if you are currently running it, simply rerun the installer, and select the "Uninstall" button. OR, click Control Panel > Programs > Programs and Features (Windows 10/11) and uninstall as you would any other application from your system.